LC-8 Hazardous Gas Detection Controller
8-Channel Wall-Mount Hazardous Gas Monitor Controller
The LC-8 controller is designed for monitoring remote 4-20 mA gas sensor/transmitters or similar devices. This instrument can be connected to any combination of up to eight sensor/transmitters for monitoring oxygen, toxic or combustible gases.
- Digital display of all channels simultaneously
- User-programmable alarms and high capacity relays
- Up to 8 4-20 mA inputs & outputs
- 100-240 VAC, 24 VDC power options
- Lockable painted steel enclosure
- Designed for 24 VDC battery backup
- IP65 Ingress Rating
Display: Digital display simultaneously shows readings for each channel and sensor type
Inputs, up to Eight: 4-20 mA, 2-wire, 3-wire or 4-wire (consult factory), 24 VDC provided
Alarm Levels: 2 user-programmable alarms per channel, and 1 common alarm
Audible Alarm: An audible alarm is provided by a horn mounted within the enclosure providing a local audible tone during alarm conditions
Visual Indicators: Red Alarm LED; Yellow Fault Alarm LED; Green Power On LED
Temperature Range: 14° to 122°F (-10°C to +50°C)
Relays: 2 per channel (1st & 2nd alarms); 1 system commongas alarm; 1 system fault relay
Relay Rating: 5 Amps, 240 VAC or 24 VDC
Outputs: 4-20 mA per channel
Power: 100-240 VAC or 24 VDC
Enclosure: Lockable, wall-mount steel enclosure, powder coated to RAL7035, IP65 ingress rating
Ingress Rating: IP65
Size: 11.8 H x 19.7 W x 3.2 D inches (300 x 500 x 80 mm)
Weight: 17 lbs. (7.7 kg)
- 1-3 Butadiene (C4H6)
- 2-Butanone (MEK) (C4H80)
- Acetaldehyde (CH3CHO)
- Acetone (CH3)2CO
- Acetonitrile (CH3CN)
- Acetylene (C2H2)
- Ammonia (NH3)
- Arsine (AsH3)
- Benzene (C6H6)
- Boron trichloride (BC13)
- Bromine (Br2)
- Butane (C4H10)
- Carbon Dioxide (CO2)
- Carbon monoxide (CO)
- Chlorine (Cl2)
- Chlorine dioxide (CLO2)
- Combustible Gas
- Disilane (Si2H6)
- Ethane (C2H6)
- Ethyl alcohol (C2H5OH)
- Ethylene (C2H4)
- Ethylene oxide (ETO) (C2H4O)
- Fluorine (F2)
- Gasoline
- Heptane (C7H16)
- Hexane (C6H14)
- Hydrazine (N2H4)
- Hydrocarbons
- Hydrogen (H2)
- Hydrogen bromide (HBr)
- Hydrogen chloride (HCl)
- Hydrogen cyanide (HCN)
- Hydrogen fluoride (HF)
- Hydrogen sulfide (H2S)
- Isobutane (C4H10)
- Isobutylene (C4H8)
- Isopropanol (CH3) CHOH
- Isopropyl alcohol (IPA) (C3H8O)
- Jet Fuel (JP8)
- Kerosene
- Methane (CH4)
- Methanol (CH3OH)
- Methyl alcohol (CH3OH)
- Methyl chloride (CH3Cl)
- Methyl ethyl ketone (MEK) (C4H8O)
- Methylene chloride (CH2Cl2)
- Natural Gas
- Nitric oxide (NO)
- Nitrogen dioxide (NO2)
- Octane (C8H18)
- Organic solvents
- Oxygen (O2)
- Ozone (O3)
- Pentane (C5H12)
- Phosphine (PH3)
- Propane (C3H8)
- Propylene (C3H6)
- Propylene oxide (C3H6O)
- Silane (SiH4)
- Solvents
- Styrene (C8H8)
- Sulfur dioxide (SO2)
- Toluene (C7H8)
- Vinyl chloride Chloroethene(VCM) (C2H3Cl)
- Volatile Organic Compounds (VOCs)
- Xylene (C8H10)
Calibration Equipment:
Calibration equipment for the LC-8 controller is dependent upon the type of sensor/transmitter included with the controller. Calibration equipment should be purchased according to the sensor/transmitter calibration equipment requirements. Contact ENMET with model numbers and serial numbers of both the LC-8 controller and the sensor/transmitters associated with the controller when inquiring about calibration equipment.
System Options and Accessories
Several accessories can be purchased with the LC-8 controller and corresponding sensor/transmitter. Listed are some of the more common items purchased:
Part No. Description
04546-004 Splash Guard for EX Series: 5120, 5155, 5165, 5175 & 5185 Sensor/Transmitters
04546-005 Splash Guard for EX-5100 Sensor/Transmitters
04546-006 Splash Guard for EX-5150-MOS Sensor/Transmitters
04546-007 Splash Guard for EX-5130 Sensor/Transmitters
04546-010 Splash Guard for EX-6100 Sensor/Transmitters
04566-014 Battery Backup, 24 VDC, 24 amp/hour
62020-002 Strobe Light, Red, 12-72 VDC
62020-003 Strobe Light, Red, 120 VAC
NOTE: Other system options available, consult factory for more information.